Power Requirements
Standard 120V, 15 amp receptacle
Diagnostics
Microprocessor-based programmable logic controller with an LCD color display operator interface
Dimensions
Width: 30 inches (varies depending on connectors used)
Height: 14 inches to main
platform
22 inches overall
Depth: 14 inches (not including the extending outlets)
Portability: The tester is not specifically designed to be portable, but may be used as a portable device if desired. It is recommended that the tester be secured to a solid platform.
Testing Connectors
The PD Tester will test only non-active cables and panels. Connecting live power cables to the tester will damage the tester.
· Straight-blade 120V-15A (common household outlet/plug)
· Twist-lock 120V-20A (NEMA L5-20)
· Twist-lock 240V-50A (Hubble)
· Twist-lock 120/208V-20A 3-phase (NEMA L21-20)
· Pin and sleeve 120/208V-100A 3-phase (blue Hubble)
· Optional Connectors: Any commercially available connector, or customer-provided panel-mount connector can be added to the tester.
Display
The display is a color LCD touch screen and serves as the primary user interface.
· 4.38" x 3.29" viewable screen size (6" x 5" total)
· 10,000 hour back light
· 1,000,000 touch operations
· Temperature: 0-55 °C
· Humidity: 20-85% (non-condensing)
Circuit Protection
Redundant circuit protection:
· Opto-electric isolation relays protect the computer
· ½ amp fast-blow fuses protect the isolation relays
Self Diagnostics
When the PD Tester is turned on, a self diagnostic routine is activated to check the integrity of the input circuitry. Additionally, both the PLC and the Display microprocessors perform a self-diagnostic routine.